{"id":3539,"date":"2026-11-21T03:52:08","date_gmt":"2026-11-21T03:52:08","guid":{"rendered":"https:\/\/yocl.com\/?wpr2_import=2be0dc29c9b8e8012d4c174bd799fcbdf3352cc5f46ccf0e76111b59a21da279"},"modified":"2026-11-21T03:52:08","modified_gmt":"2026-11-21T03:52:08","slug":"cable-gland-certificates-ukca-atex-iecex-nec","status":"publish","type":"post","link":"https:\/\/yocl.com\/es\/cable-gland-certificates-ukca-atex-iecex-nec\/","title":{"rendered":"Certificados de pasacables por mercado: UKCA, ATEX, IECEx y NEC"},"content":{"rendered":"<p>Los certificados de cable gland de \u00e1reas peligrosas UKCA, ATEX, IECEx y NEC (UL 2225) no son intercambiables entre fronteras, incluso cuando el cuerpo de lat\u00f3n y la geometr\u00eda del sello interno son id\u00e9nticos. El acceso legal al mercado depende de la jurisdicci\u00f3n que rige el sitio: Gran Breta\u00f1a regula los accesorios Ex bajo el SI del Reino Unido 2016\/1107, la Uni\u00f3n Europea exige la Directiva ATEX 2014\/34\/UE, los proyectos internacionales dependen del esquema voluntario IECEx 02, y los sitios en Estados Unidos requieren una lista NRTL reconocida por OSHA bajo los Art\u00edculos NEC 500\u2013506.<\/p>\n<p>Especificar un cable gland Ex d o Ex e solo por el nombre del producto conduce directamente a fallos en las inspecciones del sitio, retenciones en aduanas o re-trabajos forzados en paneles. Un certificado ATEX de la UE sin una auditor\u00eda de fabricaci\u00f3n activa (QAN) no puede legalmente colocar nuevo stock en el mercado europeo, un Certificado de Conformidad IECEx por s\u00ed solo no satisface a una Autoridad de Jurisdicci\u00f3n (AHJ) de EE. UU. que inspecciona un recinto de Clase I Divisi\u00f3n 1, y ignorar un sufijo X en un certificado puede anular la calificaci\u00f3n de barrera a prueba de llamas en el momento en que el cable es fijado.<\/p>\n<h2>Certificados de Cable Gland UKCA, ATEX, IECEx y NEC: Matriz Mercado por Mercado<\/h2>\n<p>Cada mercado de ubicaci\u00f3n peligrosa vincula el cumplimiento del cable gland a un instrumento legal espec\u00edfico, un organismo de certificaci\u00f3n acreditado y una cadena de documentos emparejados que cubren tanto el dise\u00f1o del producto como el control de calidad continuo de la f\u00e1brica. Tratar estos cuatro reg\u00edmenes como etiquetas equivalentes es el error de adquisici\u00f3n m\u00e1s com\u00fan en los env\u00edos de exportaci\u00f3n y paquetes EPC internacionales.<\/p>\n<table>\n<thead>\n<tr>\n<th>Mercado Objetivo<\/th>\n<th>Ley o Esquema Regulador<\/th>\n<th>Autoridad Certificadora<\/th>\n<th>Par de Documentos Obligatorios<\/th>\n<th>Marcado del Cuerpo Requerido<\/th>\n<th>Trampa de Aceptaci\u00f3n Cruzada<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Gran Breta\u00f1a (Inglaterra, Escocia, Gales)<\/td>\n<td>Reino Unido SI 2016 No. 1107 (UKEX) + GB CE reglas de reconocimiento<\/td>\n<td>Cuerpo Aprobado del Reino Unido (o Cuerpo Notificado de la UE bajo el reconocimiento de GB CE)<\/td>\n<td>Certificado de Examen de Tipo del Reino Unido + QAN del Reino Unido (o archivo ATEX de la UE v\u00e1lido) + DoC<\/td>\n<td>UKCA + c\u00f3digo UKEX (o CE + hex\u00e1gono Ex bajo el reconocimiento de GB)<\/td>\n<td>Irlanda del Norte no acepta UKCA independiente; NI requiere CE o CE + UKNI<\/td>\n<\/tr>\n<tr>\n<td>Uni\u00f3n Europea y EEE<\/td>\n<td>Directiva ATEX 2014\/34\/UE<\/td>\n<td>Cuerpo Notificado de la UE (4-d\u00edgito ID de NB)<\/td>\n<td>Certificado de Examen de Tipo de la UE + QAN ATEX activo + DoC de la UE<\/td>\n<td>CE + 4-d\u00edgito ID de NB + hex\u00e1gono Ex + Grupo\/Categor\u00eda<\/td>\n<td>El CoC IECEx independiente no autoriza legalmente la colocaci\u00f3n de bienes en el mercado de la UE<\/td>\n<\/tr>\n<tr>\n<td>Internacional \/ Offshore \/ ANZ \/ Medio Oriente<\/td>\n<td>Esquema de Equipos Certificados IECEx 02<\/td>\n<td>Organismo de Certificaci\u00f3n IECEx (ExCB) y Laboratorio de Pruebas (ExTL)<\/td>\n<td>CoC IECEx + ExTR (Informe de Prueba) + QAR activo<\/td>\n<td>n\u00famero de certificado IECEx + IEC 60079 marcado Ex<\/td>\n<td>Esquema internacional voluntario; la ley local en la UE o EE. UU. a\u00fan anula solo IECEx<\/td>\n<\/tr>\n<tr>\n<td>Estados Unidos (Ubicaciones Peligrosas)<\/td>\n<td>NFPA 70 (NEC) Art\u00edculos 500\u2013506; UL 2225<\/td>\n<td>NRTL reconocido por OSHA (por ejemplo, UL, CSA, Intertek)<\/td>\n<td>Listado NRTL activo \/ Certificado de Cumplimiento + Dibujo de Control<\/td>\n<td>Marca NRTL + Clasificaci\u00f3n\/Divisi\u00f3n o calificaci\u00f3n de Zona AEx<\/td>\n<td>Los certificados ATEX e IECEx por s\u00ed solos no superan la inspecci\u00f3n NEC sin un listado NRTL<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Antes de emitir una orden de compra para un panel de exportaci\u00f3n o skid, aseg\u00farese de bloquear primero la jurisdicci\u00f3n de destino y requiera el par de certificados exactos que coincidan con el mercado; nunca acepte un PDF ATEX como prueba de cumplimiento con el NEC de EE. UU. o un CoC IECEx como sustituto legal para la marcaci\u00f3n CE de la UE.<\/p>\n<figure class=\"wp-block-image\">\n  <img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/yocl.com\/wp-content\/uploads\/2026\/11\/four-market-ex-certification-map.webp\" alt=\"Four-column certification architecture comparing UKCA SI 2016 1107, EU ATEX 2014 34 EU, global IECEx 60079, and US NEC UL 2225 certifying bodies and document chains\" width=\"1920\" height=\"1080\" \/><figcaption>The four hazardous-area cable gland regimes differ in legal authority and required audit paperwork, even where the underlying EN IEC 60079 test methods overlap.<\/figcaption><\/figure>\n<h2>EU ATEX (2014\/34\/EU) vs UKCA \/ UKEX (SI 2016\/1107): Great Britain vs Northern Ireland<\/h2>\n<p>EU ATEX Directive 2014\/34\/EU and Great Britain UK SI 2016 No. 1107 share the same technical safety baseline\u2014EN IEC 60079-0 for general requirements, EN IEC 60079-1 for flameproof Ex d, EN IEC 60079-7 for increased safety Ex e, and EN IEC 60079-31 for dust Ex t\u2014but diverge in legal jurisdiction and conformity markings.<\/p>\n<p>Buyers shipping into the United Kingdom must separate two distinct legal territories on the same packing list:<\/p>\n<ul>\n<li><strong>Great Britain (England, Scotland, Wales):<\/strong> Regulated under UK SI 2016\/1107. Products assessed by a UK Approved Body carry a UK-Type Examination Certificate (commonly referred to as UKEX) and the UKCA mark. Under UK government indefinite CE recognition measures aligned with EU product safety frameworks, compliant CE-marked ATEX cable glands backed by valid EU Notified Body files also retain an accepted market route in Great Britain\u2014though end-user project specifications in oil, gas, and utilities may still contractually request UKCA\/UKEX paperwork.<\/li>\n<li><strong>Northern Ireland:<\/strong> Continues to operate under the Windsor Framework aligned with EU ATEX Directive 2014\/34\/EU. Cable glands placed on the Northern Ireland market require CE marking (via an EU Notified Body) or CE + UKNI marking (when assessed by a UK body for the NI market); standalone UKCA marking is not valid in Northern Ireland.<\/li>\n<\/ul>\n<p>In both the EU and UK, third-party Type Examination is mandatory for Category 1 and Category 2 (Zone 0\/1\/20\/21) cable glands\u2014including virtually all Ex db flameproof and Ex eb increased-safety cable glands\u2014and must be accompanied by the manufacturer Declaration of Conformity (DoC) citing the exact product series and standard editions.<\/p>\n<h2>IECEx Certified Equipment Scheme: CoC, ExTR and QAR Explained<\/h2>\n<p>The IECEx 02 Certified Equipment Scheme is an international conformity system administered by the International Electrotechnical Commission to eliminate redundant hazardous-area testing across participating countries such as Australia, New Zealand, Singapore, Middle East oil and gas operators, and global offshore projects. Unlike ATEX, which is a regional European law, IECEx is a standardized global certificate system built on three publicly traceable records:<\/p>\n<ol>\n<li><strong>Certificate of Conformity (CoC):<\/strong> The headline electronic certificate issued by an IECEx Certification Body (ExCB), published live in the official IECEx online database so any buyer or inspector can verify its status (Current, Suspended, or Cancelled) by certificate number in seconds.<\/li>\n<li><strong>IECEx Test Report (ExTR):<\/strong> The underlying laboratory evidence issued by an accepted IECEx Testing Laboratory (ExTL) documenting impact, thermal endurance, clamping pull-out, explosion pressure, and ingress protection tests under the IEC 60079 series.<\/li>\n<li><strong>Quality Assessment Report (QAR):<\/strong> The ongoing factory surveillance audit confirming that the manufacturing plant maintains a hazardous-location quality management system compliant with ISO\/IEC 80079-34.<\/li>\n<\/ol>\n<p>Because IECEx CoCs are publicly searchable online, many EPC buyers use an active IECEx number as their fastest technical sanity check\u2014yet an IECEx CoC alone does not confer legal CE marking inside the EU or replace OSHA NRTL listing on a United States jobsite.<\/p>\n<h2>North American NEC (Articles 500\u2013506) and UL 2225: Why ATEX\/IECEx Alone Fails Inspection<\/h2>\n<p>In the United States, hazardous-location cable fittings are governed by NFPA 70 (the National Electrical Code, NEC) and evaluated primarily to UL 2225 (<em>Cables and Cable-Fittings for Use in Hazardous (Classified) Locations<\/em>) by an OSHA-recognized Nationally Recognized Testing Laboratory (NRTL) such as UL, CSA, or Intertek. Submitting an ATEX or IECEx certificate without an NRTL listing mark routinely triggers an immediate red-tag rejection from the local Authority Having Jurisdiction (AHJ).<\/p>\n<p>North American approvals also introduce two physical engineering differences that catch European panel builders off guard:<\/p>\n<ul>\n<li><strong>Class\/Division (Articles 500\u2013503) vs Zone (AEx, Articles 505\u2013506):<\/strong> Traditional US industrial plants classify hazardous areas by Class (I gas, II dust, III fibers) and Division (1 continuous\/intermittent, 2 abnormal), whereas NEC Articles 505 and 506 adopt the Zone framework using AEx markings (AEx db, AEx eb). A gland listed only for Class I Division 2 cannot be installed in a Class I Division 1 flameproof entry.<\/li>\n<li><strong>Barrier sealing and thread engagement divergence:<\/strong> In Class I Division 1 installations using armored or tray cables (such as MC-HL or TC-ER-HL), NEC Article 501 and UL 2225 frequently require compound-filled barrier glands to block gas migration through cable interstices, paired with tapered NPT entry threads meeting minimum engaged-thread rules. By contrast, IEC 60079-14 allows non-barrier Ex d displacement-seal glands in Zone 1\/2 only when specific cable-construction, length, and enclosure-volume criteria are met.<\/li>\n<\/ul>\n<p>For entry thread geometry differences between parallel Metric threads and tapered NPT threads, see <a href=\"https:\/\/yocl.com\/es\/metric-vs-pg-vs-npt-cable-gland-threads\/\">Metric vs PG vs NPT cable gland threads<\/a>. For how IP66\/IP68 ingress testing interacts with hazardous-area enclosure seals, see <a href=\"https:\/\/yocl.com\/es\/cable-gland-ip-ratings-explained\/\">cable gland IP ratings explained<\/a>.<\/p>\n<figure class=\"wp-block-image\">\n  <img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/yocl.com\/wp-content\/uploads\/2026\/11\/ex-cable-gland-marking-anatomy.webp\" alt=\"Technical cross-section cutaway of an armoured explosion-proof barrier cable gland showing flameproof entry threads, internal compound barrier seal, armour clamping cone, and outer IP compression seal\" width=\"1920\" height=\"1080\" \/><figcaption>Four distinct safety zones inside a hazardous-area armoured barrier gland: flameproof entry thread engagement, internal compound or displacement barrier, armour clamping cone, and outer environmental IP seal.<\/figcaption><\/figure>\n<h2>The Two-Document Trap: QAN\/QAR Validity and Certificate Suffixes (X vs U)<\/h2>\n<p>Even when a supplier emails a genuine Type Examination Certificate or IECEx CoC, two hidden documentation traps routinely invalidate the installation at commissioning: an expired factory quality audit and an unread certificate suffix.<\/p>\n<ul>\n<li><strong>Trap 1 \u2014 Type Certificate without an active QAN or QAR:<\/strong> An EU Type Examination Certificate (ATEX) or IECEx CoC proves only that the laboratory prototype passed design testing. To legally manufacture and ship compliant Ex cable glands today, the factory must simultaneously hold a <strong>current ATEX Quality Assessment Notification (QAN)<\/strong> o <strong>current IECEx Quality Assessment Report (QAR)<\/strong> audited to ISO\/IEC 80079-34. If the QAN\/QAR has lapsed or been suspended, newly manufactured glands cannot legally carry the Ex mark.<\/li>\n<li><strong>Trap 2 \u2014 Ignoring the X vs U certificate suffix:<\/strong><\/li>\n<li><strong>Suffix X (Specific Conditions of Use):<\/strong> Signals mandatory installation constraints written inside the certificate schedule\u2014for example, restricting an unarmoured Ex cable gland to fixed installations with additional external clamping, limiting service temperature to a specific elastomeric seal range, or mandating a specific sealing washer to maintain IP66\/IP68 on thin enclosure walls.<\/li>\n<li><strong>Suffix U (Component Certificate):<\/strong> Identifies an incomplete Ex component that cannot be placed into hazardous-area service as standalone equipment; it must be incorporated into a separately certified Ex enclosure assembly whose final equipment certificate evaluates the combined thermal and flameproof boundary.<\/li>\n<\/ul>\n<h2>Pre-Order and Incoming Certificate Verification Checklist for Buyers<\/h2>\n<p>Treating hazardous-area compliance as a structured incoming inspection prevents mismatched shipments before cables are stripped and glands are torqued into enclosures. Check all six items below against both the PDF paperwork and the laser-etched or stamped marking on the physical gland body:<\/p>\n<table>\n<thead>\n<tr>\n<th>Verification Point<\/th>\n<th>What to Inspect on Paperwork<\/th>\n<th>What to Match on Physical Gland Body<\/th>\n<th>Reject \/ Hold Condition<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>1. Certificate number &amp; suffix<\/td>\n<td>Exact ATEX, UKEX, IECEx, or NRTL file number including any X or U suffix<\/td>\n<td>Laser-etched or stamped certificate reference matching the delivered model code<\/td>\n<td>Missing suffix X conditions sheet, or U component supplied where an equipment cert is required<\/td>\n<\/tr>\n<tr>\n<td>2. Certifying body ID \/ mark<\/td>\n<td>4-digit EU Notified Body \/ UK Approved Body ID, ExCB name, or OSHA NRTL listing<\/td>\n<td>Matching 4-digit ID beside CE\/UKCA mark, or matching NRTL mark<\/td>\n<td>Unverified body number, or ATEX\/IECEx supplied for a US NEC site requiring NRTL<\/td>\n<\/tr>\n<tr>\n<td>3. Protection concept<\/td>\n<td>Exact concept (Ex db, Ex eb, Ex tb, AEx db, or Class\/Div) matching enclosure<\/td>\n<td>Identical protection concept marked on the hex body<\/td>\n<td>Ex e gland installed into an Ex d flameproof enclosure entry<\/td>\n<\/tr>\n<tr>\n<td>4. Gas \/ dust group &amp; zone<\/td>\n<td>Group IIC \/ IIB (gas), Group IIIC (dust), EPL Gb\/Db, or Class I\/II Div 1\/2<\/td>\n<td>Matching gas\/dust group and EPL on body and box label<\/td>\n<td>Group IIB gland installed in a Group IIC hydrogen\/acetylene zone<\/td>\n<\/tr>\n<tr>\n<td>5. Service temperature &amp; IP rating<\/td>\n<td>Certified seal elastomer temperature window (e.g., -40 \u00b0C to +100 \u00b0C) and IP66\/IP68<\/td>\n<td>Model code and seal material match certificate schedule<\/td>\n<td>Missing thread sealing washer or wrong cable OD clamping range<\/td>\n<\/tr>\n<tr>\n<td>6. Active QAN \/ QAR &amp; DoC<\/td>\n<td>Current QAN\/QAR expiry date covering the manufacturing date + signed DoC<\/td>\n<td>Batch or date code traceable to valid surveillance audit period<\/td>\n<td>Expired QAN\/QAR or missing manufacturer Declaration of Conformity<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Hold incoming stock at QC receiving if any single gate fails\u2014especially a lapsed QAN\/QAR date, an unread X condition, or a protection-concept mismatch between an Ex e gland and an Ex d flameproof enclosure.<\/p>\n<figure class=\"wp-block-image\">\n  <img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/yocl.com\/wp-content\/uploads\/2026\/11\/ex-certificate-verification-flow.webp\" alt=\"Four-step buyer verification pipeline showing Type Certificate and X or U suffix check, active QAN or QAR audit date check, physical body marking match, and thread entry plus cable OD seal fit\" width=\"1920\" height=\"1080\" \/><figcaption>Verify hazardous-area cable glands in four sequential gates before installation: confirm the type certificate and X\/U conditions, check active QAN\/QAR validity, match physical body markings, and verify entry thread plus cable OD fit.<\/figcaption><\/figure>\n<p>For general non-hazardous gland sizing and material selection, see <a href=\"https:\/\/yocl.com\/es\/how-to-choose-a-cable-gland\/\">c\u00f3mo elegir un prensaestopas<\/a>, and for troubleshooting ingress failure after installation, see <a href=\"https:\/\/yocl.com\/es\/why-is-my-cable-gland-leaking-a-seal-by-seal-checklist\/\">why is my cable gland leaking<\/a>. When sourcing hazardous-area or armoured entries from YOCL ELECTRIC\u2014such as <a href=\"https:\/\/yocl.com\/es\/explosion-proof-cable-glands-manufacturer\/\">explosion-proof cable glands<\/a>, <a href=\"https:\/\/yocl.com\/es\/armoured-cable-glands-manufacturer\/\">armoured cable glands<\/a>, or specific series like <a href=\"https:\/\/yocl.com\/es\/product\/bdm-17-single-compression-armored-exd-cable-gland\/\">BDM-17 single-compression armored Ex d cable glands<\/a>, <a href=\"https:\/\/yocl.com\/es\/product\/bdm-3-single-compression-barrier-armored-cable-gland\/\">BDM-3 barrier armored cable glands<\/a>, y <a href=\"https:\/\/yocl.com\/es\/product\/bdm-1-ex-e-unarmoured-cable-gland\/\">BDM-1 Ex e unarmoured cable glands<\/a>\u2014always specify your target market (GB, EU, IECEx, or US NEC), cable construction, and entry thread so exact model-level certificates and installation conditions are verified before order confirmation.<\/p>\n<h2>Preguntas frecuentes<\/h2>\n<h3>Does an IECEx certificate automatically allow selling or installing a cable gland in the EU?<\/h3>\n<p>No, an IECEx Certificate of Conformity is a voluntary international scheme and does not legally replace EU ATEX Directive 2014\/34\/EU compliance. To place a hazardous-area cable gland on the European Union market, the manufacturer must hold an EU Type Examination Certificate (where required), an active ATEX QAN, an EU Declaration of Conformity, and apply CE plus Ex marking.<\/p>\n<h3>Can an ATEX or IECEx cable gland be used in a US NEC Class I Division 1 area?<\/h3>\n<p>No, an ATEX or IECEx certificate alone does not satisfy United States OSHA and NEC Article 500\u2013506 inspection requirements. Hazardous-location cable glands installed in the United States require an active listing from an OSHA-recognized NRTL\u2014typically evaluated to UL 2225\u2014matching the site Class\/Division or AEx Zone classification and barrier-sealing rules.<\/p>\n<h3>What is the difference between an ATEX QAN and an IECEx QAR?<\/h3>\n<p>Both documents verify that the cable gland factory operates an audited hazardous-location quality management system aligned with ISO\/IEC 80079-34. A QAN (Quality Assessment Notification) is issued by an EU Notified Body (or UK Approved Body for UKEX) to maintain ATEX\/UKEX production approval, whereas a QAR (Quality Assessment Report) is issued by an ExCB under the international IECEx scheme.<\/p>\n<h3>What does the letter X at the end of an ATEX or IECEx cable gland certificate number mean?<\/h3>\n<p>The suffix X indicates Specific Conditions of Use listed inside the certificate schedule. For cable glands, X conditions commonly restrict unarmoured glands to fixed installations requiring additional external cable clamping, define exact elastomeric service temperature limits, or mandate specific entry sealing washers to preserve enclosure ingress protection.<\/p>\n<h2>Referencias<\/h2>\n<ol>\n<li><a href=\"https:\/\/eur-lex.europa.eu\/eli\/dir\/2014\/34\/oj\" target=\"_blank\" rel=\"noopener\">EU Directive 2014\/34\/EU (ATEX)<\/a> \u2014 <em>Equipment and protective systems intended for use in potentially explosive atmospheres<\/em> (Official Journal of the European Union).<\/li>\n<li><a href=\"https:\/\/www.legislation.gov.uk\/uksi\/2016\/1107\/contents\" target=\"_blank\" rel=\"noopener\">UK SI 2016 No. 1107<\/a> \u2014 <em>The Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations 2016<\/em> (UK Legislation).<\/li>\n<li><a href=\"https:\/\/www.iecex.com\/certified-equipment-scheme\/overview\/\" target=\"_blank\" rel=\"noopener\">IECEx Certified Equipment Scheme (IECEx 02)<\/a> \u2014 <em>International Electrotechnical Commission System for Certification to Standards Relating to Equipment for Use in Explosive Atmospheres<\/em> (IECEx).<\/li>\n<li><a href=\"https:\/\/www.osha.gov\/nationally-recognized-testing-laboratory-program\" target=\"_blank\" rel=\"noopener\">OSHA Nationally Recognized Testing Laboratory (NRTL) Program &amp; UL 2225 Scope<\/a> \u2014 <em>US Occupational Safety and Health Administration<\/em> and NFPA 70 (NEC) Articles 500\u2013506.<\/li>\n<li>ELECTRIC \u2014 YOCL <a href=\"https:\/\/yocl.com\/es\/explosion-proof-cable-glands-manufacturer\/\">Explosion-Proof Cable Glands Manufacturer<\/a><\/li>\n<li>ELECTRIC \u2014 YOCL <a href=\"https:\/\/yocl.com\/es\/how-to-choose-a-cable-gland\/\">C\u00f3mo elegir un prensaestopas<\/a><\/li>\n<li>ELECTRIC \u2014 YOCL <a href=\"https:\/\/yocl.com\/es\/cable-gland-ip-ratings-explained\/\">Explicaci\u00f3n de los grados de protecci\u00f3n de los prensaestopas IP: IP65 frente a IP66 frente a IP68 (y IP69K)<\/a><\/li>\n<li>ELECTRIC \u2014 YOCL <a href=\"https:\/\/yocl.com\/es\/metric-vs-pg-vs-npt-cable-gland-threads\/\">Rosca m\u00e9trica vs PG vs NPT para prensaestopas<\/a><\/li>\n<li>ELECTRIC \u2014 YOCL <a href=\"https:\/\/yocl.com\/es\/why-is-my-cable-gland-leaking-a-seal-by-seal-checklist\/\">\u00bfPor qu\u00e9 pierde mi prensaestopas? Una lista de comprobaci\u00f3n sello a sello<\/a><\/li>\n<\/ol>","protected":false},"excerpt":{"rendered":"<p>Hazardous-area cable gland certificates UKCA, ATEX, IECEx, and NEC (UL 2225) are not interchangeable across borders even when the brass body and internal seal geometry are identical. Legal market access depends on which jurisdiction enforces the site: Great Britain governs Ex fittings under UK SI 2016\/1107, the European Union mandates ATEX Directive 2014\/34\/EU, international projects [&hellip;]<\/p>\n","protected":false},"author":2,"featured_media":3538,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[161],"tags":[],"class_list":["post-3539","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-cable-glands"],"_links":{"self":[{"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/posts\/3539","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/comments?post=3539"}],"version-history":[{"count":1,"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/posts\/3539\/revisions"}],"predecessor-version":[{"id":3540,"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/posts\/3539\/revisions\/3540"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/media\/3538"}],"wp:attachment":[{"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/media?parent=3539"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/categories?post=3539"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/yocl.com\/es\/wp-json\/wp\/v2\/tags?post=3539"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}