YOCL

HSC-B 4:1 Semi-Rigid Dual-Wall Heat Shrink Waterproof End Cap

YOCL Electric HSC-B semi-rigid dual-wall heat shrink end caps seal, insulate and mechanically protect cable terminations.

  • Nominal 4:1 shrink ratio with a pre-sealed closed end.
  • Radiation cross-linked polyolefin outer wall and hot-melt adhesive lining.
  • Five black models with supplied I.D. limits from ≥3.2 mm to ≥12.7 mm.
  • Initial shrink temperature ≥80°C; full shrink temperature ≥135°C.
  • Operating range -45°C to +110°C; breakdown strength ≥22 kV/mm.
Renseignez-vous sur ce produit

Aperçu

YOCL Électrique HSC-B 4:1 Semi-Rigid Dual-Wall Heat Shrink Waterproof End Cap seals, insulates and mechanically protects cable ends and wire-harness terminations. It combines a semi-rigid radiation cross-linked polyolefin outer wall with an internal hot-melt adhesive lining.

The pre-sealed closed end covers the cable termination, while the open end allows installation over the cable. During heating, the cap recovers and the adhesive flows around the cable surface. After cooling, the adhesive-lined closed-end construction helps form a waterproof and moisture-resistant seal. Five standard models provide a nominal 4:1 shrink ratio.

Caractéristiques

  • Semi-rigid outer wall: Provides structural and mechanical protection around cable terminations.
  • Closed-end design: Covers the cable end with a pre-sealed outer wall.
  • Dual-wall adhesive sealing: Combines polyolefin insulation with a hot-melt adhesive lining.
  • Nominal 4:1 recovery: Supports installation over a cable termination before shrinking around the cable.
  • Electrical insulation: Specified breakdown strength is ≥22 kV/mm.
  • Five black models: Supplied and recovered diameters, A/B lengths and wall thicknesses are listed below.

Spécifications techniques

Parameter Specification
Brand YOCL Électrique
Series HSC-B
Product type Semi-rigid dual-wall heat shrink waterproof cable end cap
Construction Dual wall / semi-rigid / closed end
Shrink ratio 4:1 nominal
Outer material Radiation cross-linked polyolefin
Inner layer Hot-melt adhesive
Initial shrink temperature ≥80°C
Full shrink temperature ≥135°C
Température de fonctionnement -45°C to +110°C
Standard color Black
Environmental standard RoHS
Water absorption <0.50%
Number of listed models 5

Mechanical Performance

Property Specification Test method or condition
Tensile strength ≥12 MPa ASTM D2671
Elongation at break ≥300% ASTM D2671
Tensile strength after aging ≥9 MPa 158°C for 168 hours
Elongation after aging ≥100% 158°C for 168 hours
Axial change -8% to +8% ASTM D2671

Thermal Test Performance

Test Condition Result
Thermal shock 225°C for 4 hours No cracks or dripping
Cold bending -40°C for 4 hours No crack

The thermal-shock, cold-bending and aging temperatures describe test conditions. The operating temperature range is -45°C to +110°C.

Electrical Performance

Property Specification Test method
Breakdown strength ≥22 kV/mm IEC 60243
Volume resistivity ≥1 × 10¹⁴ Ω·cm IEC 60093

Dimension

HSC-B 4:1 Semi-Rigid Dual-Wall Heat Shrink Waterproof End Cap dimension drawing

Model Nominal size (mm) Standard length (A/B) (mm) Supplied I.D. (mm) Max. I.D. after recovery (mm) Total wall thickness (mm) Outer wall thickness (mm) Adhesive layer thickness (mm)
HSC-B-3 Ø3.2 22.0 / 12.7 ≥3.2 ≤0.80 1.20 0.64 0.56
HSC-B-4 Ø4.8 29.5 / 15.2 ≥4.8 ≤1.20 1.52 0.76 0.76
HSC-B-6 Ø6.4 31.4 / 15.2 ≥6.4 ≤1.52 1.91 1.00 0.91
HSC-B-9 Ø9.5 39.8 / 18.3 ≥9.5 ≤2.00 2.08 1.08 1.00
HSC-B-12 Ø12.7 35.1 / 21.6 ≥12.7 ≤2.41 2.54 1.30 1.24

All listed dimensions are in millimetres. I.D. means internal diameter. Supplied I.D. values are minimum limits, and recovered I.D. values are maximum limits. Standard lengths retain the A/B notation.

Selection Guide

Select a model with a supplied I.D. large enough to pass over the cable termination. Review its specified maximum recovered I.D., A/B length values and wall thicknesses for the area to be covered.

Use the listed diameter limits to assess fit. For example, HSC-B-9 has a minimum supplied I.D. of 9.5 mm and a maximum recovered I.D. of 2.00 mm. Its total wall thickness is 2.08 mm, comprising 1.08 mm outer wall and 1.00 mm adhesive layer.

Check installation temperatures separately from the service range. Initial shrink is specified at ≥80°C and full shrink at ≥135°C; the operating range is -45°C to +110°C.

Applications

  • Power cable ends and electrical cable terminations.
  • Wire-harness ends and unused cable ends.
  • Moisture-sensitive cable-end insulation and sealing.
  • Cable storage and transportation protection.
  • Mechanical protection of cable terminations.

Installation Notes

  1. Select an HSC-B model using the cable-end diameter and dimensional table.
  2. Ensure the termination is clean and suitable for adhesive sealing.
  3. Slide the open end of the cap over the termination and position the closed end to cover the cable end.
  4. Apply controlled heat evenly until the outer wall has recovered and the adhesive has flowed around the cable.
  5. Remove the heat source and allow the assembly to cool completely.
  6. Inspect the recovered cap and final seal.

Ordering Information

Specify HSC-B, the required model and quantity when making an enquiry to YOCL Electric. Available models are HSC-B-3, HSC-B-4, HSC-B-6, HSC-B-9 and HSC-B-12, with black as the standard color.