EL Ribbed Support Insulators

EL ribbed support insulators use an unsaturated polyester BMC body and brass nut inserts.

  • Six listed part numbers.
  • Heights from 60 to 210 mm.
  • Rated voltages from 3.6 to 24 kV, depending on model.
  • Model-specific creepage, low-frequency dielectric and impulse voltage data.
  • Dark brown or dark red.
  • Top and bottom insert arrangements listed by part number.
Tanyakan tentang produk ini

Tinjauan

YOCL ELECTRIC EL ribbed support insulators combine an unsaturated polyester bulk moulding compound body with brass nut inserts. The ribbed body profile and insert arrangement vary by model. Dark brown and dark red colours are listed.

Six part numbers are specified, with heights from 60 to 210 mm and listed rated voltages from 3.6 to 24 kV. Rated voltage, low-frequency dielectric strength and impulse voltage resistance are provided as separate characteristics for each model.

Fitur

  • Unsaturated polyester BMC body with a ribbed profile.
  • Brass nut inserts in model-specific arrangements.
  • Six part numbers with 60–210 mm heights.
  • Model-specific creepage distance and electrical data.
  • Dark brown or dark red colour.

Spesifikasi Teknis

Parameter Spesifikasi
Seri EL ribbed support insulators
Bahan Unsaturated polyester Bulk Moulding Compound (BMC)
Nut inserts Brass; various specifications listed
Warna Dark brown or dark red
Test specification references as listed JIS C3801; JIS C3851

Electrical Characteristics

Part number Rated voltage (kV) Low-frequency dielectric strength (kV) Impulse voltage resistance (kV)
76:120 10 55 110
EL-24 24 60 125
EL-15 15 50 110
EL-12 12 36 95
EL-6M 7.2 22 75
EL-3M 3.6 16 60

Mechanical Characteristics

Part number Sustained bending strength, 1 min (source unit: kg) Tensile strength (source unit: kg) Torque strength (source unit: kg-m)
76:120 400 1500 25
EL-24 300 >1500 >25
EL-15 400 >1500 >25
EL-12 300 >2000 >25
EL-6M 400 >1200 >25
EL-3M 400 >1200 >25

The mechanical figures retain the source unit labels kg and kg-m; no force-unit conversion is applied. The greater-than signs are part of the listed specifications. Torque strength is not a recommended installation tightening torque.

Dimensi

EL Ribbed Support Insulators dimension drawing

EL Ribbed Support Insulators dimension drawing

Part number End diameters A/B (mm) Height H (mm) Creepage distance (mm)
76:120 76 120 300
EL-24 70 210 356
EL-15 70 142 210
EL-12 58 130 172
EL-6M 70 90 125
EL-3M 70 60 88

Insert Arrangement

Part number Top A1 Top A2 Top A3 Top AX (mm) Top AY (mm) Bottom S1
76:120 M16 –/M8 – – – –
EL-24 M10/M12 – M6/M8 – 36/40 M10/M12/M16
EL-15 M8/M10 – M6/M8 – 36/40 M10/M12/M16
EL-12 M10 M8 – 36 – M10/M16
EL-6M M10 M8 – 40 – M10
EL-3M M10 M8 – 40 – M10

A1, A2 and A3 identify the top insert positions; S1 is the central bottom insert position. AX and AY retain the labelled top spacing values. A dash represents an unlisted position or dimension. Slash-separated entries retain the available designations in the source and should be specified when requesting the final insert layout.

Panduan Pemilihan

Choose the part number by its rated voltage, height, end diameter and creepage distance, then specify the top and bottom insert arrangement. For example, EL-6M and EL-3M share a 70 mm end diameter, but differ in height, creepage distance and rated voltage. The part number 76:120 is retained as listed and has its own electrical and insert data.

Informasi Pemesanan

For a quotation, specify the part number, quantity, colour, top insert designation, bottom insert designation and required mounting spacings. Request the final insert layout for any slash-separated thread or spacing options.