YOCL

CW Kabelverschraubung

YOCL ELECTRIC CW Cable Glands are single-compression armoured cable glands for SWA cable installations. The catalogue lists 14 metric-size models from VO-CW20S to VO-CW75L.

  • Brass or nickel-plated brass construction with an external sheath seal and armour clamp.
  • IP66/IP67 protection grades stated for the CW series.
  • Listed operating temperature: −20 to +80 °C.
Produkt anfragen

Übersicht

YOCL ELECTRIC CW Cable Glands are single-compression armoured glands for steel wire armoured (SWA) cable. The described assembly provides an external sheath seal and an armour clamp at the enclosure entry. Fourteen metric-size CW models are listed from size 20 to 75.

Merkmale

  • External sheath seal and armour clamp: supports cable entry sealing and armour retention.
  • Brass construction: described with or without nickel plating.
  • IP66/IP67 protection grades: stated for the CW series.
  • Indoor and outdoor application: identified for SWA cable installations in the source.

Technische Daten

Parameter Spezifikation
Produktserien CW
Compression type Single compression
Cable type Steel wire armoured (SWA)
Body material Brass; nickel-plated brass option
Protection grades IP66 and IP67, as stated in the catalogue
Betriebstemperatur −20 to +80 °C
Referenced standard BS 6121, as stated in the catalogue
Listed models 14

Abmessung

The table gives the catalogue’s metric thread size number without a thread pitch. Its A and B column headings both say “Cable Range Max,” so the values are kept as labelled dimensions rather than treated as a minimum/maximum cable range. Lengths and A/B values are in millimeters.

Modell Metric thread size Minimum thread length D (mm) Cable A (mm) Cable B (mm)
VO-CW20S 20 10 11.8 17.8
VO-CW20L 20 10 14.0 20.8
VO-CW25S 25 10 18.0 24.0
VO-CW25L 25 10 20.3 27.4
VO-CW32S 32 10 24.5 31.0
VO-CW32L 32 10 26.5 34.2
VO-CW40S 40 13 30.4 38.5
VO-CW40L 40 13 33.2 41.0
VO-CW50S 50 13 40.0 47
VO-CW50L 50 13 44.0 53.5
VO-CW63S 63 14 50.0 59.0
VO-CW63L 63 13.5 56.0 66.0
VO-CW75S 75 15 63.5 73.0
VO-CW75L 75 15 69.0 73.0

CW Cable Gland dimension drawing

Auswahlhilfe

Select the required metric thread size, then check the SWA cable and armour measurements against the catalogue’s A and B values. Confirm the thread pitch, available engagement length and required finish before ordering.

Bestellinformationen

Provide the full CW model code, SWA cable construction and dimensions, required finish and quantity when requesting a quotation.

Projektdetails

Felder mit * sind erforderlich.

Ihre Daten werden verwendet, um auf Ihre Anfrage zu antworten. Datenschutzhinweis