YOCL

VO-4 Series Explosion-Proof Cable Gland

The VO-4 series explosion-proof cable gland uses a mechanical cable-clamping construction. The supplied catalogue lists nine models for cable outside diameters from 5–12 mm to 50–90 mm.

  • G pipe thread and metric thread references appear together in the source table; confirm the required order thread.
  • Brass or stainless steel is listed as the material choice.
  • Catalogue marking: Exd IIC Gb; catalogue protection level: IP66.
  • Model-by-model C lengths are provided for dimensional comparison.
Inquire about this product

Overview

The VO-4 series explosion-proof cable gland uses a mechanical cable-clamping device. The supplied catalogue lists brass or stainless-steel construction, nine model codes and corresponding cable diameter ranges. The Ex marking and IP rating below reflect the catalogue; project approval documents should be checked separately.

Features

  • Mechanical cable-clamping construction described in the source.
  • Nine model codes with cable outside diameter ranges and C dimensions.
  • Catalogue provides G pipe thread and metric thread references. Metric or NPT thread specifications can be produced according to the source; a particular order thread should be stated in the enquiry.

Technical Specifications

Parameter Catalogue specification
Series VO-4
Clamping Mechanical cable clamp
Material options Brass / stainless steel
Ex marking Exd IIC Gb (catalogue marking)
Protection level IP66 (catalogue value)

Models and Dimensions

Cable ranges and C are in mm. The source prints G and metric references in the same thread cell; these are alternatives to specify for an order, not two simultaneous threads on one part.

Model G pipe thread reference Metric thread reference Cable outside diameter C
VO-4-EX-10 G1/2 M20×1.5 5–12 63
VO-4-EX-14 G3/4 M25×1.5 5–16 64
VO-4-EX-18 G1 M32×1.5 10–24 74
VO-4-EX-26 G1 1/4 M40×1.5 15–28 84
VO-4-EX-30 G1 1/2 M50×1.5 18–35 86
VO-4-EX-42 G2 M63×1.5 23–45 86
VO-4-EX-55 G2 1/2 M75×1.5 35–60 100
VO-4-EX-65 G3 M88×1.5 40–70 100
VO-4-EX-80 G4 M110×1.5 50–90 100

Selection Guide

Specify the model, actual cable outside diameter, required thread type and material when enquiring. The catalogue says metric or NPT pipe threads may be produced, but does not assign separate order codes or dimensions to those options. Check the relevant approval documentation for the installation before specifying a hazardous-area product.

Dimension

VO-4 Series Explosion-Proof Cable Gland dimension drawing

VO-4 Series Explosion-Proof Cable Gland dimension drawing

Project details

Fields marked * are required.