YOCL

VO Small-Thread Large-Range Brass Cable Glands

VO Small-Thread Large-Range Brass Cable Glands use a nickel-plated brass body, PA clamping claws and NBR sealing insert and O-ring. The source catalog lists 13 model rows with cable clamping range, thread dimensions and spanner size.

  • Metric thread options in the catalog's large-range series.
  • Catalog-stated IP68 at 10 bar when installed within the specified clamping range with the O-ring tightened.
  • Static operating temperature: −40 to +100 °C; dynamic: −20 to +80 °C.
  • Use the model table to match cable outside diameter, thread and mounting hole.
Inquire about this product

Overview

VO Small-Thread Large-Range Brass Cable Glands use a nickel-plated brass body, PA clamping claws and NBR sealing insert and O-ring. The source catalog lists 13 model rows with cable clamping range, thread dimensions and spanner size. Choose the gland by cable outside diameter and the mating enclosure thread or mounting hole. The catalog describes IP68 protection at 10 bar when the O-ring is tightened and the cable remains within the specified clamping range.

Features

  • Nickel-plated brass body with metallic finish.
  • PA clamping claws and NBR sealing insert and O-ring.
  • Cable clamping ranges and mounting dimensions are listed by model.

Technical Specifications

Parameter Catalog specification
Thread family Metric
Body Nickel-plated brass
Clamping claws Nylon PA
Sealing insert and O-ring NBR
Catalog ingress protection IP68 at 10 bar, conditional on specified clamping range and tightened O-ring
Static working temperature −40 to +100 °C; short-term up to +120 °C
Dynamic working temperature −20 to +80 °C; short-term up to +100 °C

Dimension

Cable ranges are shown in ascending order (minimum–maximum); the source table prints maximum–minimum. All dimensions are in millimeters except thread designations and threads per inch. GL is thread length and H is overall joint length. This is the small-thread, large-range series; some catalog codes also appear in the standard metric series with different specifications. The two VO-M20-NP rows below are distinct catalog entries identified by their cable ranges and dimensions, not newly assigned order codes.

Model code Thread Cable OD range (mm) Thread OD (mm) Mounting hole (mm) GL (mm) H (mm) Spanner (mm)
VO-M12-NP M12×1.5 4–8 12 12–12.2 7 19 17
VO-M14-NP M14×1.5 5–10 14 14–14.2 8 21 20
VO-M16-NP M16×1.5 5–10 16 16–16.2 8 21 20
VO-M20-NP M20×1.5 10–14 20 20–20.2 8 23 24
VO-M20-NP M20×1.5 9–16 20 20–20.2 9 27 27
VO-M25-NP M25×1.5 15–22 25 25–25.2 9 29 35
VO-M32-NP M32×1.5 18–25 32 32–32.2 10 31 40/35
VO-M40-NP M40×1.5 25–33 40 40–40.2 10 36 50/45
VO-M50-NP M50×1.5 37–44 50 50–50.2 12 37 64/55
VO-M63-NP M63×1.5 42–52 63 63–63.2 13 41 78/68
VO-M72-NP M72×1.5 50–62 72 72–72.2 15 45 86/78
VO-M80-NP M80×1.5 60–70 80 80–80.2 18 46 98/86
VO-M88-NP M88×1.5 70–80 88 88–88.2 18 46 110/98

Selection Guide

Match the cable outside diameter to the clamping range, then verify the exact thread type, thread size and installation space. When requesting a quote, specify small-thread, large-range series, the catalog code, cable range and quantity. For VO-M20-NP, also specify GL, H and spanner size to distinguish the two catalog entries.

Dimension

VO Small-Thread Large-Range Brass Cable Glands dimension drawing

Proje detayları

* ile işaretlenmiş alanlar zorunludur.

Sorunuza yanıt vermek için bilgileriniz kullanılacaktır. Gizlilik bildirimi