Metric vs PG vs NPT Cable Gland Threads

Metric vs PG vs NPT Cable Gland Threads

Choose a cable gland’s mounting thread from the enclosure entry, not from the cable diameter or a “nearest size” chart. Metric, PG and NPT are different thread systems. A gland marked M20 cannot be assumed to fit a PG or NPT opening because its outside diameter looks close. If the enclosure and gland use different systems, evaluate a documented adapter or entry redesign against the mounting and sealing requirements.

For a new design, specify the enclosure entry and gland mounting thread together. For a replacement, the existing entry governs: retain a matching PG or NPT designation when its drawing and installation requirements call for it. No one family is a universal upgrade. The comparison below concerns the equipment-side entry thread; the cable-side sealing range is a separate check.

Decision point Metric (M) PG NPT
Typical gland label M20 Ă— 1.5 PG13.5 1/2 NPT
Governing thread system Metric threads used for conduit fittings under IEC 60423 Steel-conduit thread dimensions under DIN 40430 Taper pipe-thread series under ASME B1.20.1
Basic entry form Parallel Parallel/cylindrical (technical thread chart) Tapered (ASME public contents preview)
Direct-fit decision Match the complete M designation, including pitch, to a compatible entry Match the PG designation to a compatible PG entry Match the NPT designation and tapered mating entry
What the label does not establish Cable outside-diameter range, hole size or installed IP performance A metric equivalent, cable range or installed IP performance A literal inch-size outside diameter, cable range or installed IP performance

The table is a thread-identification guide, not a drilling or tapping chart. For any of the three, the final decision also depends on whether the enclosure has a tapped hole or an unthreaded clearance hole, whether the selected gland has enough usable thread length, and how the enclosure joint is sealed.

Read the designation before reading a dimension

M20 × 1.5 identifies a metric entry with a 20 mm nominal thread diameter and 1.5 mm pitch. The designation is on the mounting side of the gland; it says nothing about the diameter of cable that passes through the seal. The publicly viewable IEC 60423:2007 preview lists M20 × 1.5 in Table 1. Where a product drawing says only “M20,” confirm its actual pitch rather than completing the specification by assumption.

PG13.5 is a designation in the PG system, not a 13.5 mm major diameter and not a metric thread written another way: YOCL’s VO-PG13.5-NP catalogue row lists a 20.4 mm “thread OD” for that specific gland. DIN 40430:1971-02 is the dimensional standard for the steel-conduit thread. A project with an existing PG entry therefore needs the actual PG designation, rather than a gland chosen from a chart of approximate outer diameters. DIN Media currently lists DIN 40430 as current; do not infer from the use of metric glands in new designs that every PG thread standard or existing PG entry has disappeared.

1/2 NPT denotes an American standard taper pipe thread covered by ASME B1.20.1. The fractional label is a thread designation, not a field measurement of the complete external stem. With a tapered thread, the diameter changes along the threaded length. The NPT designation must therefore be verified as a thread designation, not inferred from one caliper reading across its crest. A lookalike straight-thread fitting is not thereby an NPT mate.

This distinction is visible in YOCL’s own catalogue. The Metric VO-M12-NP, PG VO-PG7-NP and NPT VO-NPT1/4-NP are listed with the same 3–6.5 mm cable range, but different entry designations. Their catalogue “thread OD” values are close, which makes them a useful warning against choosing by appearance:

YOCL catalogue variant Entry designation Listed “thread OD” Listed cable range
VO-M12-NP M12 × 1.5 12 mm 3–6.5 mm
VO-PG7-NP PG7 12.5 mm 3–6.5 mm
VO-NPT1/4-NP 1/4 NPT 13.6 mm 3–6.5 mm

These are product-page declarations for three specific variants, not a conversion table. The close listed outside diameters and identical cable ranges do not establish that any two threads mate. In particular, a single “thread OD” listed for a tapered NPT stem cannot describe its diameter at every axial position. Do not use this table to choose a tap, clearance-hole diameter or adapter; use the exact product and enclosure drawings for those dimensions.

Conceptual Metric, PG and NPT gland stems aligned with three separately labelled matching enclosure entries
Each gland stem needs its own correctly specified entry. Conceptual comparison, not to scale; it does not establish mating dimensions or a sealing method.

Why a close outside diameter does not make a replacement

A threaded connection needs the correct profile, pitch or lead, nominal size and axial geometry on both mating parts. IEC 60423’s metric thread figure shows a 60° flank angle; the GĂĽhring tooling chart identifies PG as 80° and NPT as 60°. Sharing a 60° angle does not make Metric and NPT compatible: their designations, pitch and straight-versus-tapered geometry still need separate matching. Even if the first turn of an unfamiliar gland appears to enter an opening, that does not show correct engagement over the required length. Continuing to tighten an unverified combination can damage the entry or leave the mounting and seal unresolved.

The practical test is not “Which PG number is closest to M20?” It is: What female entry or mounting hole does this enclosure actually provide, and what male mounting thread does the proposed gland actually have? A nominal-diameter comparison cannot answer that. Nor can a similar across-flats hexagon size: the wrench flats are not the entry thread.

When a component drawing calls out M20 Ă— 1.5, request a gland or adapter with that mating M20 Ă— 1.5 interface. When it calls out PG13.5 or 1/2 NPT, keep that exact family and size on the mating side. If the notation is missing, treat the thread as unidentified until a drawing, part record or proper gauge establishes it. Do not use a force-fit trial as the identification method.

The enclosure opening changes the replacement route

Two enclosures can show an opening of similar apparent size yet require different gland hardware. A tapped entry has a female thread in the enclosure wall or threaded boss. A clearance hole is unthreaded; a gland may pass through it and be retained with the manufacturer’s specified locknut and sealing arrangement. The second case can sometimes accommodate a different gland thread family without rethreading the enclosure, but only if the exact new gland, hole, wall thickness, locknut, engagement and sealing components are approved together. Similar hole diameter alone is not approval.

Existing interface Replacement decision Evidence to obtain before ordering
Known tapped Metric, PG or NPT entry First choose a gland with the same complete mating designation; if unavailable, assess a purpose-made adapter. Enclosure thread callout, gland or adapter drawing, usable thread length, installation and sealing instructions.
Known unthreaded clearance hole A differently designated gland may be possible without mating its thread to the panel, provided the complete mounting stack is compatible. Actual hole diameter and tolerance, wall thickness, nut access, gland shoulder and thread length, entry-seal design.
Unknown opening or mixed documentation Hold the substitution decision until the entry is identified. Enclosure drawing or part number, physical inspection, appropriate thread gauge and dimensional confirmation.

An adapter adds two interfaces, not a magic conversion: one side must mate correctly with the enclosure, the other with the gland, and the assembled joint must meet the project’s mechanical and ingress requirements. Check its thread designations, available engagement, protrusion, enclosure space and specified seals. YOCL’s cable gland accessories can be reviewed as potential components after those interfaces are defined; the presence of an accessory category does not prove a particular adapter fits or preserves a rating.

Mechanical attachment and water ingress are separate questions. A locknut may hold a gland in a clearance hole without sealing the panel face. A tapered NPT joint may use a specified sealing method, but NPT geometry by itself does not prove the IP rating of a cable-gland installation. Likewise, a straight Metric or PG thread does not tell you which washer, O-ring, face seat or other arrangement the specific product requires. Follow the enclosure, gland and accessory instructions for the actual stack; verify the completed entry against the required ingress conditions. IEC 62444:2010 describes the entry thread as the gland portion attaching it to the enclosure and calls for supplier documentation including entry-thread size/type and length, maximum clearance-hole diameter and declared degree of protection where applicable. Those are separate fields for a reason; citing the standard does not certify a YOCL model or an assembled enclosure. IEC 62444:2010 preview, definitions and §7.3.

Three decisions in real projects

A new enclosure with a documented Metric tapped entry. If the drawing specifies M20 Ă— 1.5, shortlist glands with that exact mounting designation. Confirm the female-thread detail, entry depth and available gland thread length from the respective drawings. Only then check the gland’s cable sealing range and other application needs. A PG part with a similar outside diameter is not a drop-in alternative. IEC 62444’s scope expressly covers cable glands with IEC 60423 metric entry threads; that scope statement does not establish conformity for every gland sold with an M thread. IEC 62444:2010, scope.

A replacement in a PG-equipped panel. Start from the panel or removed gland’s recorded PG designation, and confirm it against the actual entry. A matching PG gland may be the cleanest route when the existing tapped entry and enclosure construction are sound. If the project instead wants a Metric gland, decide whether a documented PG-to-Metric adapter or a properly redesigned opening is acceptable. Check the added joint and space, rather than calling two near diameters equivalent.

An imported enclosure with an NPT tapped entry. Record the full NPT callout from its drawing. Select an NPT gland with the matching designation or a documented transition fitting where the equipment design permits it. Verify engagement and the specified sealing method for that exact combination. A catalogue “1/2-inch” label, a measured stem diameter, or a washer that happened to fit another entry does not independently resolve the tapered mating geometry or the enclosure’s ingress requirement.

These are decision patterns, not installation instructions. Any change to an enclosure entry can affect the equipment’s documented construction and required approvals. Follow the responsible equipment designer’s requirements when modifying a production or certified enclosure.

Verify an unmarked entry and write a usable purchase specification

Start with the enclosure make, model and drawing revision. If a legible thread callout exists, use it rather than reverse-engineering from a rough hole measurement. If it does not, identify whether the opening is tapped or plain, inspect an undamaged representative entry, and have a competent technician verify its thread with suitable gauges and the relevant standard or a known original part. A caliper can help screen a candidate, but it cannot by itself establish thread profile, pitch or the NPT gauge position. Do not order solely from a photograph.

For a replacement request, send the supplier this compact record:

Record State the actual evidence or open question
Enclosure interface Enclosure model/drawing revision; tapped entry’s complete designation or clearance-hole diameter and tolerance.
Mounting geometry Wall thickness, usable thread depth/length, gland shoulder and locknut access, nearby obstructions.
Proposed gland Exact series and part number, entry designation and thread length from its drawing.
Transition and seal Adapter’s two full thread callouts if used; specified panel seal, thread-sealing method or other mounting accessories.
Separate cable-side check Actual cable outside-diameter range and the exact gland’s published sealing range.
Acceptance evidence Required ingress level and installation instructions for the full enclosure-entry arrangement, plus project-specific approvals if applicable.

IEC 62444’s documentation list is useful as a check against an incomplete datasheet: besides the thread and clearance hole, it distinguishes cable sealing range, installation torque if any, anchorage information, IP declaration and other product information. Ask for the fields relevant to the chosen configuration; do not infer a universal torque or IP level from this comparison article. For the wider cable, material and environmental decision after the entry is known, use YOCL’s cable gland selection guide.

When the interface record is complete, compare the matching thread options in YOCL’s cable gland range against an exact model drawing. Where a required dimension or sealing instruction is absent, keep the proposed substitution open rather than treating a nearby thread size as confirmation.

Related reading: cable gland fixing and sealing components.